Building Code Guide 12-11: Four-Story Code Guide

Information
Under what conditions may a four-story residential structure be regulated under the ORSC? We answer your questions about the application of building codes and outline optional alternates.

Building Code Guides (BCGs) provide a comprehensive alternative to a complicated set of code requirements.

BCG 12-11: Four-Story Code Guide 

QUESTION: The scope of the Oregon Residential Specialty Code (ORSC) is limited to structures not more than three stories above grade plane. Under what conditions may a four-story residential structure be regulated under the ORSC?

RESPONSE: Four story residential structures, including those with enclosed useable and/or habitable space on all four stories, may be regulated under the ORSC provided all of the following conditions are met:

  1. NFPA 13D fire sprinklers shall be installed throughout the structure, under a permit from Portland Permitting & Development. 
    • Where an ADU is present within a four-story structure, an NFPA 13-R sprinkler system shall be installed throughout the structure under a separate permit from the Fire Marshall’s Office;
  2. Four story structures with more than 2,000 square feet of total enclosed space and enclosed useable and/or habitable space on more than three stories, shall have at least two egress doors to the exterior. Each required egress door shall be located on a different story, and shall be located at grade, or be provided with access to grade via a code compliant ramp or stairway. 
    • Where an ADU is present within a four-story structure, two egress doors shall be provided from each dwelling unit having enclosed usable space on more than three stories. Each required egress door shall be located on a different story, and shall be located at grade, or be provided with access to grade via a code compliant ramp or stairway;
  3. Structures with enclosed useable and/or habitable space on four stories shall not also have a basement, a mezzanine, or a roof deck (five levels);
  4. The underside of the lowest floor shall be protected with 5/8-inch gypsum sheathing or shall be protected with additional fire sprinklers;
  5. Exposed vertical posts supporting the lowest floor shall have a minimum solid sawn size of 6-inches by 6-inches, or be of noncombustible construction, and;
  6. The structural design for the entire structure shall be prepared by a licensed design professional registered in the state of Oregon. 

HISTORY: Implemented May 1, 2012. Revised August 17, 2022.