QUESTION: Are any projections allowed into the 7' - 0" headroom clearance required in the pedestrian and vehicular circulation areas in a parking garage?
RESPONSE: Wall mounted shelves, storage surfaces, cabinets, piping, and ductwork located at the head of a parking space may encroach into the required 7' - 0" vertical headroom clearance required in a parking garage under the following conditions:
- The shelving, storage surface, cabinet, piping, or ductwork does not project more than 24" into a parking space.
- The shelving, storage surface, cabinet, piping, or ductwork has a minimum of 48" vertical clearance above the floor.
- In buildings of Type I or Type II construction the shelving, storage surface, cabinet, piping, or ductwork shall be of noncombustible material or shall be protected by automatic sprinklers as required by the Fire Marshal's Office.
- No obstruction by shelving, storage surface, cabinet, piping, or ductwork shall be permitted in spaces and aisles designated for van-accessible parking.
- No obstruction by shelving, storage surface, cabinet, piping, or ductwork shall be permitted into pedestrian circulation areas or into vehicular drive lanes or maneuvering areas.
- All piping or ductwork projecting into vehicle parking spaces shall be protected against damage by vehicle contact in a manner approved by Portland Permitting & Development.
HISTORY: Implementation. Updates August 22, 2007, March 30, 2023, and July 24, 2024.